In recent years, vegetable oil such as Palm Oil (PO) has been identified as a potential alternative dielectric insulating fluid for transformers. It is biodegradable, non-toxic and has high flash and fire points. In this paper, a study on the positive lightning impulse breakdown voltages of PO under non-uniform field is carried out. The testing was carried out using needle-plane electrodes configuration at gap distances of 25 mm and 50 mm. Rising voltage, 1 and 3 shots per step testing methods were used and 3 types of Refined Bleach and Deodorized Palm Oil (RBDPO) and Mineral Oil (MO) were examined. It was found there is no significant effect on the breakdown voltages of all samples. The breakdown voltages of all RBDPO at 50% probability are comparable with MO. At 1% probability and gap distance of 50 mm, the breakdown voltages of all RBDPO are lower than MO.


Download File

[img]
Preview
PDF
9-JTS(S)-0123-2016-4thProof.pdf

Download (1MB) | Preview

Additional Metadata

Item Type: Article
Divisions: Faculty of Engineering
Publisher: Universiti Putra Malaysia Press
Keywords: Lightning breakdown voltage; Non-uniform field; Palm oil; Transformers
Depositing User: Nabilah Mustapa
Date Deposited: 30 Jun 2017 09:52
Last Modified: 05 Jul 2017 03:31
URI: http://psasir.upm.edu.my/id/eprint/55901
Statistic Details: View Download Statistic

Actions (login required)

View Item View Item