UPM Institutional Repository

The response of a high voltage transformer with various geometries of core joint design


Citation

Alyozbaky, Omar Sh. and Mohd Isa, Maryam and Ab Kadir, Mohd Zainal Abidin and Izadi, Mahdi (2017) The response of a high voltage transformer with various geometries of core joint design. Pertanika Journal of Science & Technology, 25 (spec. Feb.). pp. 21-28. ISSN 0128-7680; ESSN: 2231-8526

Abstract

The core losses in a three phase transformer can be significantly reduced by improving the core joint geometry. The researchers were applied numerous types of T-joint designs in order to reach the optimum design that can be used in three phase transformer to reduction the losses. Two types of T-joint design are presented in this paper; T-joint with 90° butt-lap design and T-joint with 45° mitered design. A 3-phase distribution transformer was simulated in 3D using Ansys Maxwell software. The core loss for a three-leg three phase transformer rated 1000 KVA and the flux density distribution are investigated. The simulation results show the core losses were increased up to 3% and the flux density was increased to reach more than 22% flux density become higher when using T-joint with 90° butt-lap design as compared with T-joint with 45° mitered design.


Download File

[img]
Preview
PDF
3-JTS(S)-0117-2016-4thProof.pdf

Download (1MB) | Preview

Additional Metadata

Item Type: Article
Divisions: Faculty of Engineering
Publisher: Universiti Putra Malaysia Press
Keywords: Core loss; Power transformer; Joints design; Flux distribution
Depositing User: Nabilah Mustapa
Date Deposited: 30 Jun 2017 09:50
Last Modified: 05 Jul 2017 03:36
URI: http://psasir.upm.edu.my/id/eprint/55884
Statistic Details: View Download Statistic

Actions (login required)