Citation
Babaei, Maziar and Babaei, Mehdi and Nourirad, Ghasem
(2014)
Analysis of influential factors in determining very fast transient overvoltages of GIS substations.
In: 2014 IEEE 8th International Power Engineering and Optimization Conference (PEOCO2014), 24-25 Mar. 2014, Langkawi, Kedah, Malaysia. (pp. 79-84).
Abstract
High voltage Gas Insulated Substation (GIS) is threatened by Very Fast Transient Overvoltage (VFTO) which is high amplitude and high frequency transient within the range from 100 kHz up to 50 MHz in power systems. Operation of Disconnecting Switch is the main origin of these overvoltage phenomena that is analyzed in this paper. In this study, the effects of several parameters that influence on VFTO amplitude have been discussed. The focus of this paper is on the VFTO study of "Siah-bishe" power plant 400kV GIS substation. The study was carried out by modeling all pieces of equipment in EMTP-RV and careful consideration of different modeling guidelines and instructions described in available standards.
Download File
|
Text (Abstract)
Analysis of influential factors in determining very fast transient overvoltages of GIS substations.pdf
Download (35kB)
|
|
Additional Metadata
Actions (login required)
|