UPM Institutional Repository

Effect of GIC neutral blocking devices (NBDs) on power network ferroresonance in Malaysia


Citation

Mohammed Khurshid, Zmnako and Ab Aziz, Nur Fadilah and Rhazali, Zeti Akma and Ab Kadir, Mohd Zainal Abidin (2022) Effect of GIC neutral blocking devices (NBDs) on power network ferroresonance in Malaysia. IEEE Access, 10. 77225 - 77238. ISSN 2169-3536

Abstract

Geomagnetic disturbance (GMD) arises during space weather and solar activity can result in geomagnetically induced current (GIC) flow in the grounded power transformers in the power network. This GIC may cause half-cycle saturation of transformers and lead to severe damage or blackout. To block the GIC flow into the power transformers, the neutral blocking devices (NBDs) based on capacitor banks are often installed in the neutral ground paths of transformers to mitigate the GIC. However, the high voltage (HV) can build up across these capacitors during ground faults and may cause a ferroresonance phenomenon in the power network. This phenomenon generates high voltages/currents in the transformer windings and results in transformer failure. This work investigates the effect of connected NBDs to the power transformers on the potential power network ferroresonance in Peninsular Malaysia. The complete analysis was carried out using the Power System Computer-Aided Design for Electromagnetic Transients including Direct Current (PSCAD/EMTDC) software. These transformers were selected in the power network due to the sensitivity of their locations to GMD events. The NBD systems were tested under different working conditions. The simulation results found that the metal oxide varistors (MOVs) arresters in NBDs fault protection mode effectively clamped ferroresonance overvoltages below the protection level under faulty conditions. Also, the results showed that GIC protection modes with 1 Ω and 3180 µF in the mitigation systems had the lowest ferroresonance overvoltages in the neutrals of the transformers under faulty conditions. Based on the results, the recommendations were provided to the local power utility which will help to improve the reliability of the power supply to the consumers.


Download File

Full text not available from this repository.
Official URL or Download Paper: https://ieeexplore.ieee.org/document/9800710

Additional Metadata

Item Type: Article
Divisions: Faculty of Engineering
DOI Number: https://doi.org/10.1109/ACCESS.2022.3184424
Publisher: IEEE Access
Keywords: Power transformers; Surges; Circuit faults; Ferroresonance; Capacitors; Arresters; Voltage
Depositing User: Ms. Nur Faseha Mohd Kadim
Date Deposited: 23 May 2023 07:43
Last Modified: 23 May 2023 07:43
Altmetrics: http://www.altmetric.com/details.php?domain=psasir.upm.edu.my&doi=10.1109/ACCESS.2022.3184424
URI: http://psasir.upm.edu.my/id/eprint/101110
Statistic Details: View Download Statistic

Actions (login required)

View Item View Item